CSB Battery HR1218W 12V Valve Regulated Sealed Lead Acid Type
As a 12V valve regulated sealed lead acid battery, the CSB HR1218W combines pure lead construction with AGM technology, making it suitable for data center UPS and other applications requiring high rate discharge. The 15-minute rate power reaches 17.8 W/cell, while the 5-minute rate is 38.1 W/cell, with a float charge design life of up to 5 years.
Taobao store
WeChat procurement
Product Features
- VRLA (Valve Regulated Lead Acid) battery
- Maintenance-free, utilizing AGM (Absorbent Glass Mat) technology with gas recombination efficiency up to 99%
- Pure lead construction with proprietary element formulation
- Specifically developed for high-rate UPS and float charge backup power applications
- Manufactured in accordance with IEC 61056-1/2:2012 and certified to UL1989 (MH14533)
Application Scenarios
- UPS backup power for small and medium data centers
- Uninterruptible power supply for server racks
- Emergency power protection for network equipment rooms
- Uninterruptible power backup for medical imaging equipment
- Fast discharge scenarios for industrial control UPS
- Backup power for precision laboratory instruments
Product parameters
- Model:HR1218W
- Voltage:12 Vdc
- Nominal Capacity:18W @15min-rate
- Watts per Cell:38.1 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:17.8 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:1.80 A
- Max. Discharge Current:130 A
- Internal Resistance:28.5 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.53 / 3.37 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):51.0±1.0 / 2.01±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HR1218W is a 12V valve regulated sealed lead acid battery in the HR series of high rate discharge pure lead batteries, positioned by the manufacturer for small-output UPS and fast-discharge backup power applications. At 1.67 VPC @25°C, its nominal capacity is expressed as 18W at the 15-minute rate; the 5-minute rate power reaches 38.1 W/cell, and the 15-minute rate power is 17.8 W/cell, making it suitable for backup power scenarios requiring high power output over a short period.
This battery uses a valve regulated sealed lead acid structure combined with Absorbent Glass Mat technology, achieving gas recombination efficiency of up to 99%, and is a maintenance-free design overall. The positive and negative plates are made with pure lead construction and a proprietary formula, which helps high rate discharge performance. The case is made of ABS material with a flame retardant rating meeting UL 94-HB; a 94-V0 flame retardant version can also be supplied if required. The product complies with IEC 61056-1/2:2012 and is recognized under UL1989.
In terms of electrical specifications, the HR1218W has a nominal voltage of 12 Vdc, a maximum charge current of 1.80 A, a maximum discharge current of 130 A, and an internal resistance of 28.5 mΩ. At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalization charge voltage range is 14.4 to 15.0 Vdc/battery. The terminal uses F2-Faston Tab250. After standing for 90 days at 25°C, the self-discharge rate is less than 10%, and it can be stored for up to 6 months; it must be fully charged before use, and if the storage temperature exceeds 25°C, it should be charged sooner.
In terms of mechanical dimensions, the battery measures 150.9±2.0 mm in length, 51.0±1.0 mm in width, and 98.6±1.0 mm in height, with a weight of approximately 1.53 kg. Operating temperature range: nominal 25°C, discharge from -15°C to 50°C, and charge and storage from -15°C to 40°C. Under float charge at 25°C, the design life is up to 5 years; under the Eurobat standard at 20°C, it is 3 to 5 years.
Data center uninterruptible power supply systems are the main application for the HR1218W, providing short-duration high rate backup power for critical loads. With its maintenance-free characteristics and compact size, it is easy to integrate into UPS cabinets with limited space. To ensure performance and lifespan, the specified charge voltage and temperature ranges should be observed during use.