CSB Battery UPS123606 12V 360W Valve Regulated Sealed Lead Acid Type
The CSB UPS123606 is a 12V Valve Regulated Sealed Lead Acid battery in the UPS series, with a nominal capacity of 360W at the 5-minute rate. Combining a pure lead construction with AGM technology, it primarily serves the float charge backup needs of data center uninterruptible power supplies.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) technology
- AGM (Absorbent Glass Mat) design, maintenance-free, with gas recombination efficiency up to 99%
- Pure lead construction with proprietary elements
- Engineered for high-rate UPS and float charge backup power applications
- Manufactured to IEC 61056-1/2:2012 and UL1989 certified (MH14533)
Application Scenarios
- UPS backup battery — for data centers
- Uninterruptible power supply — server room applications
- Industrial UPS high-power backup
- UPS emergency power — for medical equipment
- UPS backup — for financial systems
- UPS backup — for telecom room requirements
Product parameters
- Model:UPS123606
- Voltage:12 Vdc
- Nominal Capacity:360W @5min-rate
- Watts per Cell:57.83 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:27.83 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:3.00 A
- Max. Discharge Current:130 A
- Short Circuit Current:325 A
- Internal Resistance:20.70 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.97 / 4.34 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):51.0±1.0 / 2.01±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 100 A (5 sec.)
Product details
The UPS123606 belongs to CSB's UPS series product line, covering 6V and 12V top terminal VRLA-AGM types, with the officially designated application being data center uninterruptible power supplies. This model has a nominal voltage of 12 Vdc and a nominal capacity calculated at 9.60V per PCS @ 25°C, reaching 360W at the 5-minute rate. In high-rate discharge UPS float charge backup scenarios, its power output is: 57.83 W/cell at 5 minutes 1.67 VPC @ 25°C, and 27.83 W/cell at 15 minutes 1.67 VPC @ 25°C.
In terms of electrical characteristics, the UPS123606 has a maximum charge current of 3.00 A, a maximum discharge current of 130, a short-circuit current of 325 A, and an internal resistance of 20.70 mΩ. The float charge voltage range is 13.5 to 13.8 Vdc/battery (25°C), and the equalization charge voltage is 14.4 to 15.0 Vdc/battery (25°C). Regarding operating temperature, the nominal temperature is set at 25°C (77°F), discharge can cover -15°C to 50°C (5°F to 122°F), and the charge and storage temperature range is -15°C to 40°C (5°F to 104°F).
This battery uses F2 terminal Faston Tab 250 terminals, with a case material of ABS (UL 94-HB), and a flame-retardant 94-V0 model can also be provided upon customer request. In terms of dimensions, the length is 150.9±2.0 mm, width 51.0±1.0 mm, height 98.6±1.0 mm, and weight 1.97 kg. For design life, under 25°C float charge backup conditions it can reach up to 5 years, and the Eurobat (20°C) standard commercial life is 3 to 5 years.
Structurally, it adopts a Valve Regulated Sealed Lead Acid (VRLA) design, requires no maintenance, and is paired with Absorbent Glass Mat (AGM) technology, with gas recombination efficiency of up to 99%; combined with a pure lead construction and proprietary elements, it is specifically built for high-rate UPS float charge backup power applications. It is manufactured in accordance with IEC 61056-1/2:2012 and has obtained UL1989 recognition (MH14533).
Self-discharge performance: stored at 25°C (77°F) for 90 days, self-discharge is less than 10%, and it can be stored for up to 6 months; it must be fully charged before use, and if the storage temperature exceeds 25°C (77°F), it needs to be charged earlier. The above parameters can serve as a reference when selecting models for float charge backup scenarios such as data center UPS.