CSB Battery 12V 200W HRL12200W VRLA
As a 12V VRLA battery, the CSB HRL12200W belongs to the HRL high rate pure lead series, delivering 200W at the 15-minute rate and 385W per cell at the 5-minute rate, primarily serving data center UPS float backup power.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) design
- Maintenance-free, utilizing Absorbent Glass Mat (AGM) technology with up to 99% gas recombination efficiency
- Pure lead construction with proprietary element formulation
- Engineered for high-rate UPS and float charge backup power applications
- Manufactured to IEC 60896-21/22:2004 and certified to UL1989 (MH14533)
Application Scenarios
- Backup power for large data center UPS
- Backup power for high-voltage DC in cloud computing centers
- Uninterruptible power for financial trading systems
- Emergency power for telecom hub UPS
- High-power backup for industrial automation UPS
- Backup power for rail transit signal UPS
Product parameters
- Model:HRL12200W
- Voltage:12 Vdc
- Nominal Capacity:200W @15min-rate
- Watts per Cell:385 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:218 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:20.0 A
- Max. Discharge Current:400 A
- Short Circuit Current:1509 A
- Internal Resistance:5.50 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:17.30 / 38.13 kg / lb.
- Length (L):228.0±2.5 / 8.98±0.10 mm / in
- Width (W):138.4±1.5 / 5.45±0.06 mm / in
- Height (H):206.3±2.5 / 8.12±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HRL12200W is a product of the HRL series, featuring a 6V plus 12V top terminal design, and is a VRLA battery. It utilizes AGM Absorbent Glass Mat technology with a gas recombination efficiency of up to 99%, requiring no maintenance during normal operation. The battery has a nominal voltage of 12 Vdc, and at the 15-minute rate at 1.67 VPC, 25°C, the nominal capacity is expressed as 200W; also at 1.67 VPC, 25°C, the 5-minute rate power per cell is 385 W/cell, and the 15-minute rate is 218 W/cell.
In terms of electrical parameters, the HRL12200W allows a maximum charging current of 20.0 A, a maximum discharge current of 400 A, a short-circuit current of 1509 A, and an internal resistance of only 5.50 mΩ. At 25°C, the float charge voltage ranges from 13.5 to 13.8 Vdc/battery, and the equalize charge voltage ranges from 14.4 to 15.0 Vdc/battery. Regarding self-discharge, it remains below 10% after 90 days of storage; it can be stored for up to 6 months at 25°C, but must be fully charged before use. If the storage temperature exceeds 25°C, a supplementary charge should be performed in advance.
The battery uses I2 threaded lead alloy terminals, compatible with M6 bolts, with a terminal torque of 51.7±10.3 Kgf·cm or 44.9±9.0 Lbf·in or 5.10±1.0 N·m. The case material is PP (UL 94-HB), and a flame-retardant 94-V0 version is available upon request. Dimensions are 228.0±2.5 mm in length, 138.4±1.5 mm in width, and 206.3±2.5 mm in height, with a weight of 17.30 kg.
The HRL series is positioned as long-life, high rate UPS pure lead batteries, primarily addressing high-power data center and UPS loads. Under float charge at 25°C, the HRL12200W has a design life of up to 10 years; according to the Eurobat (20°C) standard, it exceeds 12 years, classified as a very long life level. In terms of temperature adaptability, the nominal temperature is 25°C, the discharge range is -15°C to 50°C, and the charge and storage range is -15°C to 40°C.
The officially designated application area is data center uninterruptible power supply, suitable for high rate UPS and float backup power scenarios. This model is manufactured in accordance with IEC 60896-21/22:2004 and has been recognized under UL1989 (MH14533). Thanks to the pure lead construction and proprietary formulation elements, it maintains stable performance under both float backup and high rate discharge requirements.