Product Features

  • VRLA (Valve Regulated Lead Acid) battery
  • AGM (Absorbent Glass Mat) technology, maintenance-free, up to 99% gas recombination efficiency
  • Pure lead construction with proprietary elements
  • Developed for high-rate UPS and float charge backup power applications
  • Manufactured to IEC 61056-1/2:2012, UL1989 certified (MH14533)

Application Scenarios

  • Large-scale UPS backup power for data centers
  • High-voltage DC backup power for cloud computing rooms
  • Uninterruptible power protection for financial trading platforms
  • UPS emergency power support for telecom hubs
  • High-power UPS backup for industrial automation
  • UPS backup power for rail transit signaling systems

Product parameters

  • Model:HRL1225W
  • Voltage:12 Vdc
  • Nominal Capacity:25W @15min-rate
  • Watts per Cell:54.16 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:25.67 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:2.50 A
  • Max. Discharge Current:130 A
  • Short Circuit Current:328 A
  • Internal Resistance:19.60 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:1.95 / 4.30 kg / lb.
  • Length (L):90.0±1.0 / 3.54±0.04 mm / in
  • Width (W):70.0±1.0 / 2.76±0.04 mm / in
  • Height (H):106.1±1.5 / 4.18±0.06 mm / in
  • Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB HRL1225W is a 12V Valve Regulated Sealed Lead Acid battery in the HRL series. It uses Absorbent Glass Mat (AGM) technology with gas recombination efficiency of up to 99%, and features a pure lead construction with a proprietary element formula. The series is positioned for high-rate UPS and float standby power, with data center uninterruptible power supplies listed as the official application. In terms of specifications, the HRL1225W has a nominal capacity of 25W @15-minute rate, tested at 1.67VPC, 25°C. The 5-minute rate power is 54.16 W/cell, and the 15-minute rate power is 25.67 W/cell. Its maximum charge current is 2.50 A, maximum discharge current is 130 A, short-circuit current is 328 A, and internal resistance is 19.60 mΩ. The float charge voltage range is 13.5 to 13.8 Vdc/battery (25°C), and the equalize charge voltage range is 14.4 to 15.0 Vdc/battery (25°C). Dimensions and terminals: the battery measures 90.0±1.0 mm in length, 70.0±1.0 mm in width, and 106.1±1.5 mm in height, and weighs 1.95 kg (4.30 lb). The terminal is F2 terminal - Faston Tab 250. The case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version is available on request. For temperature conditions, the nominal temperature is 25°C (77°F); discharge is permitted from -15°C to 50°C (5°F to 122°F), and charge and storage are permitted from -15°C to 40°C (5°F to 104°F). Self-discharge performance: after 90 days at 25°C, self-discharge is less than 10%, and storage is possible for up to 6 months; the battery should be fully charged before being put into service, and if the storage temperature exceeds 25°C, a supplementary charge is required in advance. In terms of life design, it can be used for 8 years under float charge at 25°C; according to the Eurobat (20°C) standard, it is 10 to 12 years. The product is manufactured in accordance with IEC 61056-1/2:2012 and is UL1989 recognized (MH14533). With its maintenance-free construction and high-rate discharge performance, the HRL1225W is well suited for scenarios requiring reliable backup power, such as data center UPS.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat
Loading...